Introduction
CDF-6000/12KV Automatic 12kV Capacitance & Dissipation Factor Test Set is designed to measure dissipation or power factor in heavy electromagnetic interference environment such as in power plants or substations. Also it can be used in laboratory for high accurate test. The test set is all-in-one structure: including precision digital bridge, 12kV/200mA frequency conversion power unit, reference capacitor (CN), and other electronic circuits.
Technical Parameter
Accuracy: Cx: ±(readingx1%+1pF); tanδ: ±(readingx1%+0.00040)
Anti-Interference: the above accuracy met even at 200% times of interference.
Capacitance Range: Internal HV: 3pF~60000pF/ 10kV, 60pF~1uF/0.5kV
External HV: 3pF~1.5uF/10kV, 60pF~30uF/0.5kV
Resolution: 0.001pF, 4 digits.
Tan δ range: no limit, resolution: 0.001%; capacitance, inductance and resistance auto recognized.
Test current range: 10μA-5A
Internal high voltage:
Set range: 100v-10000v; 100v-12000v;
Output current: maximum 200mA;
Voltage smoothly regulated;
voltage accuracy: ±(reading*1%);
voltage resolution: 1v
Test frequency: 45~65Hz, step 1Hz;
49Hz/51Hz, 59Hz/61Hz, auto dual frequency.
Frequency accuracy: ±0.01Hz
External High voltage:
Positive connection, max test current is 5A;
Negative connection max test current: 10000v/5A;
Test frequency: 30-300Hz
Test time: 30 seconds (relative with test mode)
Power Supply: 110V/220V, 50/60Hz (other optional input: 180v-270vAC)
Printer: micro printer
Communication Port: RS-232, (wireless Bluetooth port optional)
Operating Temperature:-10℃~50℃
Humidity: <90% non-condensing
Dimensions: 46cm (L)*35cm (W)*34cm (H)
Weight: Main unit: 28kg, cable: 3.5kg